MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Master Programming Level
Annunciator addressing is specific to the FACP control panel.  The following table describes the 
annunciator addresses and the corresponding addressable devices that will be annunciated at each 
annunciator address. 
The 8 General System Status Points include the following:
General Alarm
General Trouble
General Supervisory
Alarm Silenced
System Off Normal
AC  Loss
Battery Fault
NAC Fault
Pressing 3 while viewing the ACS Options screen will toggle the display between UDACT NO and 
UDACT YES.  This allows the connection of an external UDACT (Universal Digital Alarm Com-
municator/Transmitter).
ACS Annunciator Address
Annunciator Displays the Following Points
1
8 General System Status Points & Zones 1 - 56
2
Zones 57 - 99 & 4 NACs
3
Loop 1, Module Addresses 1 - 64
4
Loop 2, Module Addresses 1 - 64
5
Loop 1, Module Addresses 65 - 128
6
Loop 2, Module Addresses 65 - 128
7
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
8
Loop 1, Detector Addresses 1 - 64
9
Loop 2, Detector Addresses 1 - 64
10
Loop 1, Detector Addresses 65 - 128
11
Loop 2, Detector Addresses 65 - 128
12
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
13
not used
14
not used
15
not used
16
not used
17
not used
18
not used
19
not used
20
8 General System Status Points & Zones 1 - 56
21
Zones 57 - 99 & 4 NACs
22
Loop 1, Module Addresses 1 - 64
23
Loop 2, Module Addresses 1 - 64
24
Loop 1, Module Addresses 65 - 128
25
Loop 2, Module Addresses 65 - 128
26
Loop 1, Module Addresses 129 - 159 & Loop 2 Module Addresses 129 - 159
27
Loop 1, Detector Addresses 1 - 64
28
Loop 2, Detector Addresses 1 - 64
29
Loop 1, Detector Addresses 65 - 128
30
Loop 2, Detector Addresses 65 - 128
31
Loop 1 Detector Addresses 129 - 159 & Loop 2 Detector Addresses 129 - 159
32
not used