MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Product Description
Circuits
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED 
indicators as listed above.  The key panel, which is visible with the cabinet door closed, has 25 
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.
1.5  Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board.  A second SLC loop is avail-
able by plugging the optional SLC module into connector J3 on the main circuit board.  SLC loops, 
configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor 
(initiating device) and control (output device) modules.  Refer to the SLC Wiring Manual for infor-
mation on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Special Application Power
• 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum
24 VDC Battery Charger (up to 26 AH batteries)