Appendix D: FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron 
Receiver/Transmitter.  
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 
feet and enclosed within conduit or equivalently protected against mechanical injury. 
!
CAUTION:
POSSIBLE EQUIPMENT DAMAGE
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON 
MODULES ARE NOT SHOWN IN ACTUAL ORDER.  FOLLOW KELTRON MANUAL AND MODULE 
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE!
   Fire Alarm Control Panel
(terminal blocks are not shown in their actual 
positions in order to clarify wiring connections)
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Note: Cut TBL jumper on 4XTMF module to send 
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble Signal
Sprinkler 
Supervisory Signal
*Note: For more 
information, refer to 
Keltron manual.
4XTMF Module
24 VDC 
nonresettable power
UL Listed
8th Edition Only
UL Listed
8th Edition Only
Tip
Tip
Ring
Ring
Earth
Earth
Telephone Line
Figure D.1  Wiring to Keltron Printer
To Power 
Supply
To Central/
Remote 
Station