Master Programming Level
Programming
ANN-I/O Options
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-I/O 
option is selected will display the following screen:     
The first screen indicates that the ANN-I/O at the selected ANN-BUS address is programmed to 
annunciate SLC Loop #1 addressable modules with addresses 1 through 30.  The programming can 
be changed using ANN-I/O Address Screens 2 and 3.
Pressing 1 while viewing ANN-I/O Address Screen #2 will program the annunciator module to 
annunciate either Point (addressable device address) information or Zone information.
Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be 
annunciated (refer to the tables in “ANN-I/O Zone Option” on page 123 and “ANN-I/O Point Option” on page 125).
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or 
addressable modules to be annunciated.
Pressing 3 while viewing ANN-I/O Address Screen #3 will select the SLC loop with the address-
able devices to be annunciated.
ANN-I/O Zone Option
If Zone is selected as the module option, the first ten LEDs on the first ANN-I/O module will dis-
play the system status information.  The remaining 30 LEDs on the first module and 40 LEDs on 
the remaining modules will display the active/alarm status of each zone in the Zone Range pro-
grammed for that particular module.  The LED assignments for each ANN-I/O module will be as 
follows. 
Module LED
ANN-I/O Module #1
Function
ANN-I/O Module #2
Function
ANN-I/O Module #3
Function
1
AC Fault
Zone 30
Zone 70
2
Fire Alarm
Zone 31
Zone 71
3
Supervisory
Zone 32
Zone 72
 ANN-I/O ADDR #
SLC 1 MOD 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
    ANN-I/O ADDR #
1=POINT/ZONE   POINT
ANN-I/O Address Screen #2
    ANN-I/O ADDR #
1=RANGE     PT001-030
2=DET/MOD         MOD
3=SLC LOOP #        2
ANN-I/O Address Screen #3