Controls and Indicators
Product Description
1.3.1  Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the 
total current available from the FACP power supply.
1.4  Controls and Indicators
LCD Display 
The FACP uses an 80-character (4 lines X 20 
characters) high viewing angle LCD display.  
The display includes a long life LED backlight 
that remains illuminated.  If AC power is lost and 
the system is not in alarm, the LED backlight will 
turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
1     
2     
3   
4    
5     
6    
7    
8
1     
2     
3   
4    
5     
6    
TB4
TB3
Figure 1.1  Current Availability
p
owe
rd
ist96
00
ls2
.w
mf
*The combined output current of all Special Applications Power circuits cannot exceed 1.5 amps in standby.  Each 
circuit is capable of delivering the full 1.5 amps individually.
Refer to the battery calculations section for additional information.
1.5 amps max
per circuit
1.5 amps max
per circuit
1.5 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
Standby
1.5 Amps Max*
per panel
Resettable Special 
Application Power
for 4-wire smoke detectors
Alarm
7 Amps Max
per panel
Resettable Special 
Application Power
Power #1
Resettable Special 
Application Power
Power #2
NAC 1
Style Y or Z
NAC 2
Style Y or Z
NAC 3
Style Y only
NAC 4
Style Y only
     HONEYWELL
    LIFE SAFETY
 SYSTEM ALL NORMAL
 10:00A 020102