Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
113
Master Programming Level
Programming
To program Relay 1 or Relay 3, press the number corresponding to the selected relay.  Note that 
Relay 2 is fixed as a Trouble relay.  Selecting Relay 2 will have no effect on its programming.  The 
following screen will appear for each relay to be programmed:
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be dis-
played:
While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay.  The choice will be stored in memory and the display will return 
to the Relay Type Screen which will show the programmed type choice.  Press the Escape key to 
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Note the following: 
1. AR (AutoResettable) in SUPERVISORY AR and PROCESS MON AR means that a relay with 
the Supervisory and/or Process Monitor type code, when activated, will automatically reset 
when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and 
deactivate when the FACP Alarm Silenced LED is illuminated.
Canadian Option
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Cana-
dian requirements.  The display will change to Canadian Opt. On.  Each press of the 1 key will 
cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important!  For Canadian Applications, this option must be set to ON prior to any other panel pro-
gramming.
     RELAY #
1=TYPE
              ALARM
Relay Type Screen
     RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen  #1
     RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
Relay Screen #3
     RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen  #2
     RELAY
1=MEDICAL
2=SILENCEABLE ALARM
Relay Screen #4
   SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
     SYSTEM SETUP
1=CANADIAN OPT.  OFF
2=WATERFLOW SIL.  NO