Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
167
Read Status
Operating Instructions
4.22.8  Program Check
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be 
displayed:
Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any 
input zones have not been programmed to one of the Notification Appliance Circuits.  Use the up 
and down arrow keys to view all NACs.
Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any 
output zones have not been programmed to at least one input zone.  Use the up and down arrow 
keys to view all zones.
Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any 
input zones have not been programmed to at least one output zone.  Use the up and down arrow 
keys to view all zones.
4.22.9  History
Pressing 3 while viewing Read Status Screen #3 will display the following screen:
The operator can view all events which have been stored in the history file, only alarms or other 
events, such as troubles or supervisories, by pressing the corresponding number key.
4.22.10  Annunciators
Pressing 1 while viewing Read Status Screen #4 will display the following screens:
    PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
      HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
    READ STATUS
1=ANNUNCIATORS
2=PHONE LINES
3=CENTRAL STATION
Read Status Screen #4
    ANNUNCIATORS
TERM ENABLED     YES
2=ACS OPTIONS
3=ANN-BUS OPTIONS
Annunciator Screen