Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
175
Calculating the System Current Draw
Power Supply Calculations
‘Secondary’ refers to the control panel’s backup batteries
All currents are given in amperes (A).  Table 5.2 shows how to convert milliamperes and 
microamperes to full amperes. 
5.3.2  How to Use Table 5.3 on page 176 to Calculate System 
Current Draw
Use Table 5.3 on page 176 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns.
2. Enter the current draw where required.  Refer to the Device Compatibility Document for 
compatible devices and their current draw.
3. Calculate the current draws for each in all columns.
4. Sum the total current for each column.
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 177.
Following are the types of current that can be entered into Table 5.3 on page 176:
Calculation Column 1 - The primary supply current load that the control panel must 
support during a non-fire alarm condition, with AC power applied. 
Calculation Column 2 - The primary supply current load that the control panel must 
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm 
condition during a loss of AC power.
To convert...
Multiply
Example
Milliamperes (mA) to
amperes (A)
mA x 0.001
3 mA x 0.001 = 0.003A
Microamperes (µA) to
amperes (A)
µA x 0.000001
300 µA x 0.000001 = 0.0003 A
Table 5.2  Converting to Full Amperes