Relays
Installation
2.2.3  Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited. 
2.3  Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble 
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).  
The Alarm and Supervisory silk-screen labels reflect the factory default programming for the two 
programmable relays.
Note that relay connections must be power-limited.  Refer to Power-limited wiring requirements.
2.4  Notification Appliance Circuits
The control panel provides four Style Y/Class B or two Style Z/Class A NACs (Notification Appli-
ance Circuits).  Each circuit is capable of 3.0 amps of current.  Total system current in alarm cannot 
exceed 7.0 amps (refer to “Calculating the System Current Draw” on page 174).  Use UL listed 24 
VDC notification appliances only.  Circuits are supervised and power-limited.  Refer to the Device 
Compatibility Document for a listing of compatible notification appliances.  The NACs, which are 
located on the main circuit board, may be expanded via the FCPS Series field charger/power sup-
plies. 
Figure 2.4  Special Application Power Outputs - 24 VDC
1    2    3    4    5    6
Power-limited Resettable Power
1.5 amperes max., 24 VDC nominal 
filtered, resettable power can be drawn 
from TB3 Terminals 1(+) and 2(-)
Power-limited Nonresettable Power #1
1.5 amperes max., 24 VDC nominal 
filtered, nonresettable power can be 
drawn from TB3 Terminals 3(+) and 4(-)
Power-limited Nonresettable Power #2
1.5 amperes max. , 24 VDC nominal 
filtered, nonresettable power can be drawn 
from TB3 Terminals 5(+) and 6(-)
96
0
0t
b
3.
wmf
Figure 2.5  Relay Terminals
Relay contacts shown with power applied to panel 
and no active troubles, alarms or supervisories
TB5
Note that the relays labeled as Alarm 
Relay (Relay 1) and Supervisory Relay 
(Relay 3) reflect the factory default 
programming for these relays which are 
programmable.  
The relay labeled Trouble Relay (Relay 2) 
is fixed and cannot be changed.  It is a fail-
safe relay which will transfer on any trouble 
or total power failure.