Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
57
Optional Modules and Devices
Installation
8. When the installation has been complete, enable the 4XTMF module by sliding the disconnect 
switch to the left
9. Test system for proper operation   
2.6.3  Auxiliary Trouble Input (J16 & J17)
Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the FACP main circuit board, 
can be used to monitor for trouble conditions on auxiliary equipment such as power supplies.  J16 
and/or J17 can be connected to any open collector trouble output on the auxiliary equipment.  The 
control panel will indicate a trouble condition if a trouble is sensed at the Auxiliary Trouble Inputs.
If the 4XTMF Module is installed and FACP jumper JP6 has been cut to supervise it, Auxiliary 
Trouble Input 1 (J17) will monitor the 4XTMF for trouble conditions.
2.6.4  SLC-2LS Expander Module
The optional SLC-2LS Expander Module provides a second SLC loop for the FACP control panel.  
This allows connection of an additional 318 addressable devices, bringing the total to 636 address-
able devices which can be connected to the FACP.  Refer to the SLC Wiring Manual for informa-
tion on connecting devices to the SLC.
IMPORTANT!  When SLC wiring is run in conduit, each SLC loop must be installed in separate 
conduit.
The following steps must be followed when installing the SLC-2LS Expander Module:
1. Remove all power (AC and DC) from the FACP before installing the SLC-2LS module
2. Remove four screws from main FACP motherboard, from locations indicated in following 
illustration, and replace with four supplied metal standoffs
NOTE: Jumper JP5 on the FACP main circuit board can be used to configure the FACP 
supervisory relay for operation with the 4XTMF module.  The supervisory relay must be 
programmed as shown on the main circuit board silk-screen (TB5, Terminals 4, 5 & 6).
Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP5 in will prevent generation of a trouble if the supervisory contact opens
Figure 2.16  4XTMF Connectors to FACP Connectors
J10 & J11 Connectors
Cut Jumper JP6
Standoff
Standoff
4XTMF
FACP
96
04
xtm1
.w
m
f