Honeywell m7415 Manual Do Utilizador

Página de 32
PRODUCT DATA
63-2484-2
Solid State Economizer System
(CONSISTING OF: C7046C DISCHARGE AIR SENSOR OR C7150B MIXED AIR SENSOR, C7400A 
SOLID STATE ENTHALPY SENSOR OR C7650A SOLID STATE TEMPERATURE SENSOR, M7415 
OR M8405 DAMPER ACTUATORS OR MODULATING DIRECT COUPLED ACTUATORS (MS7505), 
T6031H THERMOSTAT AND W7459 OR W7212 SOLID STATE ECONOMIZER LOGIC MODULE)
APPLICATION
The Solid State Economizer System provides an economical 
method of providing cooling air by incorporating outdoor air in 
the first stage of cooling in heating, ventilating and air 
conditioning (HVAC) systems. The Solid State Economizer 
System consists of the C7046C Discharge Air Sensor or 
C7150B Mixed Air Sensor, C7400A Solid State Enthalpy 
Sensor or C7650A Solid State Temperature Sensor, M7415 
or M8405 Damper Actuators or Modulating Direct Coupled 
Actuators (MS7505), T6031H Thermostat and W7212 or 
W7459A,C Solid State Economizer Logic Module.
FEATURES
C7046C Discharge Air Sensors have probe lengths of 8 in. 
(203 mm) and nominal sensor resistance of 3000 ohms at 
77°F (25°C).
• No setting or calibration required.
• Solid state components not affected by dust or dirt.
• Fast reacting.
• Rugged aluminum insertion probe.
C7150B Mixed Air Sensor is used with the W7212/W7459 
Economizer Module to sense mixed or discharged air in roof-
top packaged air conditioning equipment.
• No setting or calibration required.
C7400A Solid State Enthalpy Sensor and C7650A Solid State 
Temperature Sensors are used with the W7212/W7459 Solid 
State Economizer Logic Module to sense outdoor and return 
air enthalpy or temperature.
• C7400A senses and combines temperature and 
humidity (enthalpy) of outdoor air (heat index).
• C7650A senses temperature only.
• When enthalpy/temperature of outdoor air increases, 
the outdoor air damper closes to a preset minimum 
position.
• When enthalpy/temperature of outdoor air is low, the 
outdoor air damper opens to reduce the building 
cooling load.
• Additional economizer savings are achieved when two 
C7400A Solid State Enthalpy Sensors are connected to 
one Logic Module for differential enthalpy changeover 
control.
C7150B
M7415/M8405
C7046C
W7459A,C
C7400A/C7650A
W7212
T6031H
Contents
Ordering Information  ........................................................
2