H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
7
63-2579—3
CALIBRATION
All transducers are factory calibrated to meet/exceed published 
specifications. Field adjustment should not be necessary.
IMPORTANT
• Do not verify comparative RH with a sling 
psychrometer. Too many variables exist which 
induce errors into this process.
• Recalibration must be done in a controlled 
environment. Relative humidity must be held 
stable while making any adjustment.
• Verify the device output directly with calibrated 
instrumentation and verify RH with calibrated 
instrumentation. Never use a controller output.
• With correct power applied, and only a meter 
connected to the transducer output, ensure that 
the output is proportional to the true RH.
Using Increment/Decrement Switches
Increment RH Output
This DIP switch allows you to calibrate the sensor through 
the software. The switch must be toggled from the Off to 
the On position and then returned to the Off position for 
an increase of 0.5% RH. This means that if your humidity 
has drifted 1% lower over a certain time period, you can 
toggle the Increment RH Output switch (2 times) in order 
to slide the whole curve upward 1%.
Decrement RH Output
This DIP switch allows calibration in the same way as the 
Increment RH. The difference is that each toggle results 
in a decrease of 0.5% RH.
Using Calibration Trim Potentiometers
IMPORTANT
•  Due to sensitive nature of humidity calibration, 
adjusting trimmer potentiometers is not highly 
recommended.
• Calibrate only in a stable humidity/temperature 
chamber of laboratory grade.
Single Point Calibration
IMPORTANT
Use only one of the following two options.
OPTION 1
1. Select a controlled humidity environment between 
10 and 40 percent RH. Be sure humidity is stable.
2. Adjust zero trimmer (z).
OPTION 2
1. Select a controlled humidity environment between 
40 and 70 percent RH. Be sure humidity is stable.
2. Adjust span trimmer (s).
Two Point Calibration
1. Select a controlled humidity environment between 
10 and 40 percent RH. Be sure humidity is stable.
2. Adjust zero trimmer (z).
3. Select a controlled humidity environment between 
70 and 75 percent RH. Be sure humidity is stable.
4. Adjust span trimmer (s).