Bay Technical Associates BayTech DS72 Manual Do Utilizador

Página de 38
DS72 Host Module 
 
28
 
 
Type #1 for the selection, press <cr> and the Host Module responds:  
 
 
Over Voltage Alarm Threshold 
Select 4), Over Voltage Alarm Threshold and the Host Module responds: 
 
 
 
Type #1 for the selection, press <cr> and the Host Module responds:  
 
 
Low Current Alarm Threshold 
Select 5), Low Current Alarm Threshold and the Host Module responds: 
 
 
 
Type #1 for the selection, press <cr> and the Host Module responds:  
 
 
Environmental Sensors 
Select 6), Environmental Sensors with no environmental probes are attached the Host Module 
responds: 
 
 
 
If you have environmental probes attached the Host Module responds: 
 
 
 
  Sel  M/P    Identifier     Lo V Lvl    Sel  M/P    Identifier     Lo V Lvl
  1    2/1    rpc14             900      2    5/1    DS-RPC            900 
  Enter Request :1 
Enter voltage threshold value in tenths of a volt: 
  Sel  M/P    Identifier     Hi V Lvl    Sel  M/P    Identifier     Hi V Lvl
  1    2/1    rpc14            1300      2    5/1    DS-RPC           1300 
  Enter Request :1 
Enter voltage threshold value in tenths of a volt: 
  Sel  M/P    Identifier     Low Curr    Sel  M/P    Identifier     Low Curr
  1    2/1    rpc14               0      2    5/1    DS-RPC              0 
  Enter Request :1 
Enter low current threshold value in tenths of an amp: 
  None of the installed devices support this option (no temperature probes installed). 
  Strike ENTER to continue 
  Environmental Sensor Configuration Menu 
  Sel  M/P    Identifier 
  1      2/1    RPC3ADE 
  2       All Sensors 
  Enter Request :1