Description
By means of the Loop Interface LIF128-1, one ADM loop 
with bi-directional data exchange can be connected to 
Fire Detection Control Panels Series BC216. The loop 
protocol  can  be  parameterised  on  the  control  panel, 
which makes the use of different brands of detectors 
possible.
Up to
  •  318 elements with 
System Sensor/200 
protocol
– 159 detectors and 159 modules – or
  •  126 elements with 
Apollo/Discovery
 protocol or
  • 240 elements with 
Labor Strauss/700
 protocol
can be connected to a single ADM loop.
Thanks to the high maximum output current of 500mA, 
a larger number of loop elements with higher current 
demand – such as loop sounders – can also be used 
on the ADM loop.
Each ADM loop can be subdivided into a maximum of 
144 detector zones. The function of the detector zone 
– for example, manual call point zone, automatic fi re de-
tector zone, technical message or fault detection zone 
– as well as the element types of the loop elements can 
be parameterised on the fi re detection control panel.
The two loop connections of the loop interface – which 
correspond to start and end of the loop – are equipped 
with an isolator each. In the event of a short circuit, the 
isolator interrupts the loop, thus maintaining the opera-
tional reliability of those parts of the loop that are not 
affected by the short circuit.
By means of an integrated measuring and analysis func-
tion, electrical characteristics on the loop can be obtai-
ned and faults in the loop communication can be evalu-
ated. In the course of commissioning or maintenance, 
this function allows the evaluation of the transmission 
quality on the loop as well as the detection of external 
voltages, poor wiring, or of exceeding line resistances.
For this,
  • the resistance of both loop lines,
  • the loop current,
  • the loop voltage at both terminals, as well as
  • the number of faulty queries on the loop
can  be  indicated  on  the  Fire  Detection  Control  Panel 
Series BC216 since fi rmware version Vx.22.
On the control panel, you can perform a maintenance 
prognosis  for  each  connected  smoke  detector.  The 
continuous monitoring of the detector function allows 
trouble-free operation and timely recognition of detec-
tor contamination.
The loop interface is equipped with a processor of its 
own. At a possible central processing board failure, the 
diversifi ed  redundancy  concept  thus  ensures  reliable 
alarm recognition.
The fi rmware of the loop interface can be updated via 
an integrated USB interface.
•  Intelligent analogue loop technology
•   Several loop protocols for the 
detector brands System Sensor, 
Apollo and Labor Strauss
•  Up to 318 elements on the loop
•   Integrated measurement of loop 
resistance, loop current and quality 
of transmission
•  Maximum loop current 500mA