VenTing inSTallaTion
Continued
10 FOOT RULE
All flue gas outlet chimney terminations must 
extend a minimum of 3 feet in height above the 
highest point where it passes through the roof 
and must be at least 2 feet above the high-
est point of the roof that is within a horizontal 
distance of 10 feet (see Figure 20).
FINISHING FIREPLACE
Combustible  materials,  such  as  wallboard, 
gypsum board, sheet rock, drywall, plywood, 
etc. may make direct contact with sides and top 
around the fireplace face. It is important that 
combustible materials do not overlap the face 
itself. Brick, glass, tile or other noncombustible 
materials may overlap the front face provided 
they do not obstruct essential openings like 
louvered  slots  or  any  other  opening.  When 
overlapping  with  a  noncombustible  facing 
material, use only noncombustible mortar or 
adhesive.
24" Min.
24" Min.
18" 
Min.
Typ.
Figure 19 - Multiple Chase Installation
10'
2' Min.
10'
3' Min.
2' Min.
3' Min.
Level of 
Flue Gas 
Outlet
Figure 20 - 10 Foot Rule
Terminations/Spark Arrestor
The fireplace system must be terminated with 
the listed round top or chase terminations. In 
any case, refer to the installation instructions 
supplied with the termination.
 CAUTION: Do not seal open-
ings on the rooftop flashing. Fol-
low the installation instructions 
provided  with  the  termination 
being used.
Secure 
Termination 
to Outer 
Pipe with 3 
Screws
RTL-10D
Level of 
Flue Gas 
Outlet
Stainless 
Inner Flue 
Pipe
Waterproof 
Caulking
Storm 
Collar
Flashing
Underlap 
Shingles
Figure 18 - Termination
Overlap 
Shingles (Top 
and Sides of 
Flashing Base)
CHASE INSTALLATIONS
Instructions  for  chase  installations  are 
included  with  the  chase  style  termination 
chosen. In a multiple chase installation, be 
sure to provide adequate distance between 
terminations to prevent smoke spillage from 
one termination to another. We suggest that 
terminations be separated at least 24", center 
to center and stacked at a vertical height dif-
ference of 18" (see Figure 19).
Note: If a decorative shroud is to be installed, 
contact the manufacturer for specifications.