Generac 005884-1 Manual Do Utilizador

Página de 5
4 of 5
8/10/14kW
8/10/14kW 
switch options
®
Model
005870-1 (8 kW)
Model 005871-1 (10 kW)
Model 005872-1 (14 kW)
No. of Poles 
2
2
2
Current Rating (amps)
100
100
100
Voltage Rating (VAC)
250
250
250
Utility Voltage Monitor (fixed)
-Pick-up
-Dropout
80%
60%
80%
60%
80%
60%
Return to Utility
approx. 15 sec.
approx. 15 sec.
approx. 15 sec.
Exerciser weekly for 12 minutes
Standard
Standard
Standard
UL Listed
Standard
Standard
Standard
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
10
3
3
1
1
-
-
12
5
3
-
1
1
-
14
4
6
1
-
1
-
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000
10,000
10,000
EZ Switch™ Features
•  Electrically operated, mechanically-held contacts 
for fast, positive connections.
•  Rated for all classes of load, 100% equipment 
rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
•  Main contacts are silver plated or silver alloy to 
resist welding and sticking.
•  NEMA 1 (indoor rated) enclosure is standard on 
the 100 amp switch.
•  Pre-wired 30 foot (9.1 meter) whip to connect to 
the pre-wired external connection box. 
•  Pre-wired 2 foot (0.61 meter) whip, color coded to 
connect into the existing electrical panel.
Mechanical Dimensions (in inches)
Current 
Rating
No. of 
Poles
Height
Width
Depth
H1
H2
W1
W2
7
100 UL Listed
2
26.5 in
29.25 in
8.14 in
12.5 in
673mm
743mm
207mm
317.5mm
178mm
Terminal Wire Ranges
ATS Rated Amps
Switch Terminal
Neutral Lug/Stud
Ground Lug
100A 2-Pole UL
1 x 1/0-12
1 x 3/8-16 Stud
1 x 2/0-14
731.9
[28.8]
637.6
[25.1]
LEFT SIDE VIEW
642
[25.3]
76.2 [3.0]
PEA GRAVEL
MINIMUM
TRANSFER 
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER 
SWITCH
20KW
(IF SUPPLIED)
1218
[47.9]
FRONT VIEW
1226
[48.3]
H2
H1
W1
W2
H2
H1
W1
W2
®
Dimensions
Dimensions
Nexus Smart Switch™ Features 
available on 10 & 14kW models only
• Includes Digital Load Management technology standard (DLM).
• Intelligently manages two air conditioner loads with no additional hardware.
•  Up to four more large (240V) loads can be managed when used in 
conjunction with DLM modules.
•  Electrically operated, mechanically-held contacts for fast, clean 
connections.
•  Rated for all classes of load, 100% equipment rated, both inductive and 
resistive.
• Dual coil design.
• Service Rated.
• NEMA 3R aluminum outdoor enclosure.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
Model
006051-1 (10kW) / 006052-1 (14kW)
No. of Poles 
2
Current Rating (amps)
200
Voltage Rating (VAC)
250
Utility Voltage Monitor (fixed) (Function 
of Nexus Controller)
-Pick-up
-Dropout
80%
60%
Return to Utility (Function of Nexus 
Controller)
approx. 13 sec.
Exerciser weekly for 12 minutes 
(Function of Nexus Controller)
Standard
UL Listed
Standard
Enclosure Type
NEMA 3R
Withstand Rating (Amps)
10,000
Lug Range
400MCM - #4
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø 
Open Transition Service Rated
Height
Width
Depth
H1
H2
W1
W2
Inches 27.24
30.0
11.4
13.5
7.09
mm 692.0
762.4
289.0
343.0
180.0