AIR FOR COMBUSTION AND VENTILATION
 WARNING: This heater shall 
not be installed in a room or space 
unless the required volume of in-
door combustion air is provided 
by the method described in the 
National  Fuel  Gas  Code,  ANSI 
Z223.1/NFPA 54, the International 
Fuel Gas Code, or applicable lo-
cal codes. Read the following in-
structions to insure proper fresh 
air for this and other fuel-burning 
appliances in your home.
Today’s homes are built more energy efficient 
than ever. New materials, increased insulation 
and new construction methods help reduce 
heat  loss  in  homes.  Home  owners  weather 
strip and caulk around windows and doors to 
keep the cold air out and the warm air in. Dur-
ing heating months, home owners want their 
homes as airtight as possible.
While it is good to make your home energy 
efficient, your home needs to breathe. Fresh 
air must enter your home. All fuel-burning ap-
pliances need fresh air for proper combustion 
and ventilation.
Exhaust fans, heaters, clothes dryers and fuel 
burning appliances draw air from the house to 
operate. You must provide adequate fresh air 
for these appliances. This will insure proper 
venting of vented fuel-burning appliances.
PROvIDING ADEQUATE 
vENTILATION 
The following are excerpts from National Fuel 
Gas  Code. ANSI  Z223.1/NFPA  54, Air  for 
Combustion and Ventilation.
All spaces in homes fall into one of the three 
following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will 
help  you  classify  your  space  and  provide 
adequate ventilation. 
Unusually Tight Construction
The air that leaks around doors and windows 
may provide enough fresh air for combustion 
and ventilation. However, in buildings of un-
usually tight construction, you must provide 
additional fresh air. 
Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-
side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6x10
-11
 kg per pa-sec-m
2
) or 
less with openings gasketed or sealed 
and 
b.  weather stripping has been added on 
openable windows and doors and 
c.  caulking  or  sealants  are  applied  to 
areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between wall panels, at penetrations 
for plumbing, electrical and gas lines 
and at other openings.
If your home meets all of the three criteria 
above, you must provide additional fresh air. 
See Ventilation Air From Outdoors, page 7. 
If your home does not meet all of the three 
criteria  above,  proceed  to  Determining 
Fresh-Air Flow For Heater Location.
Confined Space and Unconfined Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 defines a confined space as a space 
whose volume is less than 50 cubic feet per 
1,000 Btu per hour (4.8 m
3
 per kw) of the ag-
gregate input rating of all appliances installed 
in that space and an unconfined space as a 
space whose volume is not less than 50 cubic 
feet per 1,000 Btu per hour (4.8 m
3
 per kw) 
of the aggregate input rating of all appliances 
installed in that space. Rooms communicating 
directly with the space in which the appliances 
are installed*, through openings not furnished 
with doors, are considered a part of the un-
confined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.