3.0 IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
When installing and using this electrical equipment, basic safety precau-
tions should always be followed, including:
.  WARNINg: To reduce the risk of injury, do not permit children to use 
this product unless they are closely supervised at all times.
2.  WARNINg: A grounding wire connector is provided on this unit to 
connect a minimum No. 8 AWG (8.4mm
2
) solid copper conduc-
tor between this unit and any metal equipment, metal enclosures 
of electrical equipment, metal water pipe, or conduit within 5 feet 
(.5m) of the unit.
3.  DANgER: Risk of Accidental Drowning. Extreme caution must be 
exercised to prevent unauthorized access by children. To avoid 
accidents, ensure that children cannot use this spa unless they are 
supervised at all times.
4.  DANgER: Risk of Injury. The suction fittings in this spa are sized to 
match the specific water flow created by the pump. Should the need 
arise to replace the suction fittings or the pump, be sure that the 
flow rates are compatible. Never operate the spa if the suction fit-
tings are broken or missing. Never replace a suction fitting with one 
rated less than the flow rate marked on the original suction fitting.
5.  DANgER: Risk of Electric Shock. Install at least 5 feet (.5m), from 
all metal surfaces. As an alternative, a spa may be installed within 
5 feet of metal surfaces if each metal surface is permanently con-
nected (bonded) by a minimum No. 8 AWG (8.4 mm
2
) solid copper 
conductor attached to the wire connector on the grounding lug, 
inside the equipment compartment on the equipment box.
6.  DANgER: Risk of Electric Shock. Do not permit any electrical appli-
ance, such as a light, telephone, radio, television, etc. within 5 feet 
(.5m) of a spa unless such appliances are built-in by the manufac-
turer.
7.  ELECTRICAL SUPPLY: The electrical supply for this product 
must include a suitably rated switch or circuit breaker to open all 
ungrounded supply conductors to comply with section 422-20 of the 
National Electrical Code/USA, ANSI/NFPA 70. The disconnect must 
be readily accessible and visible to the spa occupant but installed at 
least 5 feet (.5m), from the spa water.