Honeywell ms4120f Manual Do Utilizador

Página de 12
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS
5
63-2584—7
Fig. 4. Mounting shaft coupling to actuator opposite side.
Mounting
CAUTION
Device Malfunction Hazard.
Improper shaft coupling tightening causes device 
malfunction.
Tighten shaft coupling with proper torque to prevent 
damper shaft slippage.
CAUTION
Actuator Damage Hazard.
Using actuator as shaft bearing causes device 
damage.
Use actuator only to supply rotational torque. Avoid any 
side loads to actuator output coupling bearings.
To mount actuator, proceed as follows:
1. Place actuator over damper shaft; and hold mounting 
bracket in place. See Fig. 5.
2. Mark screw holes on damper housing.
3. Remove actuator and mounting bracket.
4. Drill or center-punch holes for mounting screws (or use 
no.10 self-tapping sheet metal screws).
NOTE: If necessary, use a field-fabricated steel base plate 
secured with sheet metal screws.
5. Turn damper blades to desired normal (closed) position.
6. Place actuator and mounting bracket back into position 
and secure bracket to damper box with sheet metal 
screws.
7. Using 10 mm wrench, tighten shaft coupling securely 
onto damper shaft using minimum 120 lb-in., maximum 
180 lb-in. torque.
Fig. 5. Mounting actuator to damper housing.
M20054
ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR 
ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG 
INDICATED AXIS.  WHEN TOO TIGHT, THE RESULTING  BINDING 
CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.
ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH 
THE ACTUATOR.
1
2
1
2
M20055