6
Select the item to set.
▲ ▼ → 
7
set [Failure substitution]/
[Temperature support]/[Main 
system setting].
▲ ▼ → 
 
Failure substitution
When this is set to ON, a system in 
standby mode will perform the support 
operation in case of alarm occurrence.
 
Temperature support
In Cool mode:  Performs the support 
operation when the room 
temperature exceeds “set 
temperature + set value”.
In Heat mode:  Performs the support 
operation when the room 
temperature is below “set 
temperature + set value”.
 
Main system setting
When “Set cycle” is set: System that 
performs the preceding operation
When “Set cycle” is OFF: System that 
always performs the operation
(The other system is a backup system.)
Note
 
Depending on the model, the following display 
appears and this function cannot be used.
 
Setting cycle: The day when the setting is made is counted as one day.
 
Temperature support: Immediately after the operation starts, the support 
operation is not performed for up to 1 hour.
 
Main system setting: Displays the system numbers that can be set.
Initial Settings 
 Rotation setting (Continued)
ON
OFF
No.1
No.2
•  4 to 10 °C/