22.10. T
ROUBLESHOOTING
 
The following guidelines provide instructions for fixing the most common failures and problems. Always start with the 
most likely and easiest to check condition. Some of the suggestions may require special safety precautions. See notes in 
section 2 first. 
Symptom: Action: 
“Check input voltage” LED is on 
- Check input voltage (must be between 22.8V and 30V) 
Buffer module did not buffer 
- Inhibit input was set. 
- Capacitor did not have enough time to be charged. 
Buffer module stopped buffering 
- Capacitor was discharged. 
- Capacitor did not have enough time to be charged. 
- Inhibit was activated 
- PC-mode was activated 
Output has shut down in normal mode 
- Over-temperature protection might have triggered. Let the buffer 
  module cool down. 
- PC-mode was activated (if not longer than 5s) 
Buffer module constantly switches 
between normal mode and buffer mode 
The supplying source on the input is too small and can not deliver 
sufficient current. Use a larger power supply or reduce the output load