Puls UC10.242 DIN-Rail UPS Guia De Especificação

Página de 27
 
 
UC10.241, UC10.242
 
 
UC-Series 
24V,
 
15A,
 
C
APACITOR
-
BASED 
B
UFFER 
M
ODULES
 
 
 
4.  O
UTPUT
 
 
The output section of the buffer module is fully controlled and is equipped with an electronic current limitation. A 
current overloading of the buffer module cannot happen, independent of which sizes of power supplies are used on 
the input of the buffer module. 
The current limitation works in a switching mode which reduces the power losses and heat generation to a minimum.  
 
 
Output in normal mode: 
In normal mode (and also in charging mode), the output voltage is slightly lower as the input voltage. The output 
voltage follows the input voltage reduced by the input to output voltage drop. 
 
Input to output voltage drop 
max. 
0.3V 
0.45V 
at 10A output current 
at 15A output current, see Fig. 4-1
 
Ripple & noise voltage 
max. 
30mVpp 
at 20Hz to 20MHz, 50Ohm measurement. This figure 
indicates the ripple & noise voltage which is produced 
by the buffer module. It can be higher if the supplying 
source has a higher ripple and noise voltage. 
Output current 
nom. 
15A 
continuously allowed for the entire voltage range
 
Output power 
nom. 
360W 
at 24V 
Overload behavior 
 
continuous current  see Fig. 4-2
Current limitation 
typ. 
min. 
16A 
15A 
 
Short-circuit current 
min. 17.9A 
load 
impedance 100mOhm, see Fig. 4-2
 
max. 
21.0A 
load impedance 100mOhm, see Fig. 4-2
 
Output capacitance 
typ. 
1 500μF 
included inside the buffer module 
Capacitive and inductive loads  
No 
limitation 
 
 
 
Output in buffer mode: 
The output voltage is fully regulated in buffer mode. 
The unit switches into buffer mode, when the input voltage falls below the transfer threshold input voltage level, The 
buffer voltage is slightly lower than this threshold input voltage. The unit switches back to normal mode, as soon as 
the input voltage exceeds the transfer threshold voltage, which is specified in the input section. 
 
Output voltage 
typ. 
22.45V 
±1% 
22.25V 
±1% 
22.12V 
±1%
 
at no load 
at 10A buffer current 
at 15A buffer current 
Ripple & noise voltage 
max. 
30mVpp 
at 20Hz to 20MHz, 50Ohm measurement 
Output current 
nom. 
15A 
continuously allowed
 
Output power 
nom. 
360W 
at 24V 
Overload behavior 
 
continuous current  see Fig. 4-2
Current limitation 
typ. 
min. 
16A 
15A 
Short-circuit current 
min. 
17.9A 
 
max. 
21.0A 
Capacitive and inductive loads  
No 
limitation 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/27