Puls YR2.DIODE Redundancy Module Guia De Especificação
YR2.DIODE
Y-Series
DC12-48V,
20A,
D
UAL
R
EDUNDANCY
M
ODULE
11. P
ROTECTION
F
EATURES
Output over-current protection not
included
Reverse input polarity protection included
unit does not start when input voltage is reversed
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 3.6mm
e.g. screws, small parts
Over-temperature protection
not included
Input transient protection not
included
Output transient protection
included
see EMC section
Internal input fuse not
included
12. S
AFETY
F
EATURES
Input / output separation
no galvanic separation
200V epitaxial diode between input and output
Safety level of output voltage
The output voltage is regarded to be SELV (EN 60950-1) or PELV (EN 60204-1, EN
50178, IEC 60364-4-41) if the input voltage fulfills the requirements for a SELV
source or PELV source.
50178, IEC 60364-4-41) if the input voltage fulfills the requirements for a SELV
source or PELV source.
Class of protection
III
PE (Protective Earth) or chassis connection not required
PE resistance
< 0.1Ohm
between housing and chassis-ground terminal
13. D
IELECTRIC
S
TRENGTH
The input and output voltages have the same reference, are floating and have no ohmic connection to ground.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output
terminals together before conducting the test.
When testing, set the cut-off current settings to the value in the table below.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output
terminals together before conducting the test.
When testing, set the cut-off current settings to the value in the table below.
Fig. 13-1 Dielectric strength
A
Type test
60s
500Vac
Factory test
5s
500Vac
Field test
5s
500Vac
Cut-off current setting
> 2mA
A
Chassis
In- / Output
-
+
May 2010 / Rev. 1.2 DS-YR2.DIODE-EN