22.9.  O
PERATION ON 
T
WO 
P
HASES
 
2
40V 
+10%
 max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
The power supply can also be used on two-phases of a three-phase-system. 
Such a phase-to-phase connection is allowed as long as the supplying 
voltage is below 240V+10%. Use a fuse or a circuit breaker to protect the 
N input. The N input is internally not protected and is in this case 
connected to a hot wire. Appropriate fuses or circuit breakers are specified 
in section 22.4 “External Input Protection”. 
 
22.10. U
SE 
W
ITHOUT 
PE
 ON THE 
I
NPUT
 
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2. 
Please contact PULS if you do not plan to use the PE terminal. A different marking of the front foil is then required. In 
such cases the PE terminal will change to an EMI ground terminal. Be aware that a connection to ground or earth of 
this terminal must be done in the same manner as it would be a “real” PE terminal. (wire size, isolation, …) 
Connecting this terminal can be beneficial to gain a high EMI immunity.  
Symmetrical spikes or fast transients on the input side can be conducted directly to earth by the built-in filter 
capacitors. The magnitude of such spikes or fast transients on the output side caused by the input is much smaller 
compared to not connecting this terminal to ground. 
 
 
Fig. 22-3   Earthed input 
 
Fig. 22-4   Not earthed input 
 
Surge
 
 
19/21
Y
X
L
N
EMI-ground
Power Supply
+
-
Surge
X
L
N
Power Supply
+
-
Spike
24V
 
Oct. 2009 / Rev. 1.2  DS-ML15.241-EN 
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 