Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
20/20 
27.12. M
OUNTING 
O
RIENTATIONS
 
Mounting orientations other than input terminals on the bottom and output on the top requires a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves  for continuous 
operation can be found below: 
Curve A1 
Recommended output power. 
Curve A2 
Max allowed output power (results approx. in half the lifetime expectancy of A1). 
Fig. 27-8   
Mounting 
Orientation  A  
Standard 
Orientation 
Power
Supply
OUTPUT
INPUT
 
Output Power
0
10
20
30
40
60°C
10
30
40
50W
50
A1
Ambient Temperature
20
 
 
 
 
Fig. 27-9    
Mounting 
Orientation  B 
(Upside down) 
Pow
er
Suppl
y
OUTP
UT
INPU
T
 
Output Power
0
10
20
30
40
60°C
10
30
40
50W
50
Ambient Temperature
20
A1
A2
 
 
 
 
Fig. 27-10   
Mounting 
Orientation  C  
(Table-top 
mounting) 
 
Output Power
0
10
20
30
40
60°C
10
30
40
50W
50
Ambient Temperature
20
A1
A2
 
 
 
 
Fig. 27-11   
Mounting 
Orientation  D  
(Horizontal cw) 
Po
w
er
S
uppl
y
OUT
UT
INP
U
T
 
Output Power
0
10
20
30
40
60°C
10
30
40
50W
50
Ambient Temperature
20
A1
A2
 
 
 
 
Fig. 27-12   
Mounting 
Orientation  E  
(Horizontal ccw) 
Po
w
er
S
uppl
y
OUT
UT
INP
U
T
 
Output Power
0
10
20
30
40
60°C
10
30
40
50W
50
Ambient Temperature
20
A1
A2