Puls ML60.241 Power Supply Guia De Especificação

Página de 22
 
 
ML60.241
 
 
MiniLine 
 
24V,
 
2.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
Sep. 2010 / Rev. 1.0  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
23.13. M
OUNTING 
O
RIENTATIONS
 
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous 
operation can be found below: 
Curve A1 
Recommended output current. 
Curve A2 
Max allowed output current (results in approximately half the lifetime expectancy of A1). 
 
Fig. 23-7 
Mounting 
Orientation  A 
(Standard 
orientation) 
Power
Supply
OUTPUT
 
Output Power
0
10
20
30
40
60°C
12
36
48
60W
INPUT
50
A1
24
Ambient Temperature
 
 
 
 
Fig. 23-8 
Mounting 
Orientation  B 
(Upside down) 
Powe
r
Supply
22/22
OUTPUT
INPUT
 
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
 
 
 
 
Fig. 23-9 
Mounting 
Orientation  C  
(Table-top 
mounting) 
 
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
 
 
 
 
Fig. 23-10 
Mounting 
Orientation  D  
(Horizontal cw) 
Power
Supply
OUTPUT
IN
PU
T
 
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature
 
 
 
 
Fig. 23-11 
Mounting 
Orientation  E  
(Horizontal ccw) 
Pow
e
r
Supp
ly
OUTP
UT
IN
PUT
 
Output Power
0
10
20
30
40
60°C
12
36
48
60W
50
24
A1
A2
Ambient Temperature