Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
15/21 
 
24. I
NSTALLATION AND 
O
PERATION 
I
NSTRUCTIONS
 
 
Mounting: 
Output terminal must be located on top and input terminal on the bottom. For other orientations see chapter 26.12. 
An appropriate electrical and fire end-product enclosure needs to be considered in the end use application. 
Cooling: 
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%! 
Installation clearances: 
40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when loaded permanently 
with full power. In case the adjacent device is a heat source, 15mm clearance are recommended. 
Risk of electrical shock, fire, personal injury or death! 
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth 
connection and not one of the screws on the housing. 
Turn power off before working on the power supply. Protect against inadvertent re-powering. 
Make sure the wiring is correct by following all local and national codes. 
Do not  open, modify or repair the unit. 
Use caution to prevent any foreign objects from entering into the housing. 
Do not use in wet locations or in areas where moisture or condensation can be expected. 
Service parts: 
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal defect. If damage 
or malfunctioning should occur during operation, immediately turn power off and send unit to factory for 
inspection!