The power supply can be put in series to increase the output voltage. 
 
Fig. 26-5   Schematic for series operation 
 
Instructions for use in series:
 
 
Earth
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
 
 
a) 
It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 
150Vdc. 
b) 
Voltages with a potential above 60Vdc are not SELV any 
more and can be dangerous. Such voltages must be installed 
with a protection against touching. 
c) 
For serial operation use power supplies of the same type. 
d) 
Earthing of the output is required when the sum of the 
output voltage is above 60Vdc. 
e) 
Keep an installation clearance of 15mm (left/right) between 
two power supplies  and avoid installing the power supplies 
on top of each other. 
Note: Avoid return voltage (e.g. from a decelerating motor or 
battery) which is applied to the output terminals. 
26.7. P
ARALLEL 
U
SE TO 
I
NCREASE 
O
UTPUT 
P
OWER
 
The power supply shall not be used in parallel to increase the output power. 
 
26.8. P
ARALLEL 
U
SE FOR 
1+1 R
EDUNDANCY
 
Power supplies can be paralleled for 1+1 redundancy to gain a higher system reliability. Redundant systems require a 
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two 
C-Series  power supplies in parallel. In case one power supply unit fails, the other one is automatically able to support 
the load current without any interruption. This simple way to build a redundant system has two major disadvantages: 
The faulty power supply can not be recognized. The green LED will still be on since it is reverse-powered from 
the other power supply. 
It does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a - 
situation the defective unit becomes a load for the other power supplies and the output voltage can not be 
maintained any more.  
This above conditions can be avoided by utilizing decoupling diodes which are included in the decoupling module 
YR2.DIODE or redundancy module YRM2.DIODE. 
Other recommendations for building redundant power systems: 
a) 
Use separate input fuses for each power supply. 
b) 
Monitor the individual power supply units. A DC-ok lamp and a DC-ok contact is included in the redundancy 
module YRM2.DIODE. This feature reports a faulty unit. 
c) 
When possible, connect each power supply to different phases or circuits.