Puls CS5.241 Power Supply Guia De Especificação

Página de 20
 
 
 
CS5.241, CS5.241-C1, CS5.241-S1 
 
  CSeries 
24V, 5A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Dec. 2006 / Rev. 1.3  DS-CS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
7/20 
 
10. F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 10-1   Functional diagram 
 
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
115/230V
Auto Select
 
 
 
11. R
ELIABILITY
 
 
   
AC 100V 
AC 120V 
AC 230V 
 
  Lifetime expectancy 
min. 
52 000h 
58 000h 
72 000h 
40°C, 24V, 5A 
   
min. 
27 000h 
34 000h 
42 000h 
40°C, 24V, 6A 
   
min. 
135 000h 
128 000h 
144 000h 
40°C, 24V, 2,5A 
   
min. 
142 000h 
15 years 
15 years 
25°C, 24V, 5A 
  MTBF SN 29500, IEC 61709 
638 000h 
661 000h 
869 000h 
40°C, 24V, 5A 
   
542 000h 
562 000h 
739 000h 
40°C, 24V, 6A 
   
1 077 000h 
1 111 000h 
1 495 000h 
25°C, 24V, 5A 
  MTBF MIL HDBK 217F 
552 000h 546 
000h 574 
000h 
40°C, 24V, 5A, Ground Benign GB40 
   
497 000h 
491 000h 
517 000h 
40°C, 24V, 6A, Ground Benign GB40 
   
788 000h 
775 000h 
800 000h 
25°C, 24V, 5A, Ground Benign GB25 
 
The  Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the 
lifetime expectancy of the built-in electrolytic capacitors.  
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s 
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment. 
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates 
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily 
represent the life of a product.