25.3. B
ACK
-
FEEDING 
L
OADS 
 
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called 
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). 
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power 
supply. It does not matter, whether the power supply is on or off. 
The maximum allowed feed back voltage is 35Vdc. The absorbing energy can be calculated according to the built-in 
large sized output capacitor which is specified in chapter 8. 
25.4. O
UTPUT 
C
IRCUIT 
B
REAKERS
 
Standard miniature circuit breakers (MCBs) can be used for branch protection. Ensure that the MCB is rated for DC 
voltage, too. The following tests show which circuit breakers the power supply typically trips. 
Circuit breakers have huge tolerances in their tripping behavior. Therefore, these typical tests can only be used as a 
recommendation or for comparing two different power supplies. Furthermore, the loop impedance has a major 
influence on whether a breaker trips or not. Two tests were performed, representing typical situations: 
 
Test 1: 
  Short circuit  with S1 on the power supply end of the cable (loop impedance approx. 20mOhm) 
 
Fig. 25-3   Branch protectors, test circuit 1 
 
 
Circuit
Breaker
Power
Supply
AC
DC
+
-
I
Load
+
-
S1
 
 
Parameters: 
Input voltage: 
230Vac, load current: 
0A 
 
The following circuit breaker tripped during the test: 
A- or Z- Characteristic::  equal or smaller 25A  
B- Characteristic:   
equal or smaller 16A 
C- Characteristic:   
equal or smaller 13A 
 
 
Test 2:  Short circuit with S1 on the load end (additional impedance included; represents longer load wire length). 
Fig. 25-4   Branch protectors, test circuit 2 
 
R
Circuit
Breaker
Power
Supply
AC
DC
+
-
I
S1
Load
+
-
 
 
Parameters: 
Input voltage: 
230Vac, load current: 
0A 
 
The following circuit breaker tripped during the test: 
A- or Z- Characteristic:: 
≤ 16A and R= 82mOhm 
B- Characteristic:   
≤ 6A and R= 180mOhm 
C- Characteristic:   
≤ 4A and R= 220mOhm 
 
What does this resistance mean in wire length? 
 
0.5mm
2
 0.7mm
2
 1.0mm
2
 1.5mm
2
 2.5mm
2
 4.0mm
2
 
82mOhm 
2.3m 3.2m 4.6m 6.9m 11.4m 
18.3m 
180mOhm 
5.0m  7.0m  10.0m 15.0m 25.1m 40.1m 
 
 
 
220mOhm 
6.1m  8.6m  12.3m 18.4m 30.6m 49.0m 
 
Example: 
Which wire gauge must be used to trip a B-Characteristic circuit breaker with a rating of 6A? The load wire length is 
21m. 
Answer: A 6A B-Characteristic circuit breaker requires a loop impedance of less than 180mOhm (test results). The wire 
length table shows that up to 25.1m wire with a cross section of 2.5mm
2
 are below 180mOhm. A wire not smaller 
than 2.5mm
2
 shall be used.