Puls QS10.241 Power Supply Guia De Especificação

Página de 27
 
 
QS10.241, QS10.241-A1/ -C1/ -D1
 
 
Q-Series 
24V,
 
10A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
Nov. 2011 / Rev. 2.1 DS-QS10.241-EN 
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
24.14. M
OUNTING 
O
RIENTATIONS
 
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous 
operation can be found below: 
Curve A1 
Recommended output current. 
Curve A2 
Max allowed output current (results in approximately half the lifetime expectancy of A1). 
 
Fig. 24-8 
Mounting 
Orientation  A 
(Standard 
orientation) 
Power
Supply
OUTPUT
 
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
INPUT
50
A1
Ambient Temperature
 
 
 
 
Fig. 24-9 
Mounting 
Orientation  B 
(Upside down) 
Power
Supply
27/27
OUTPUT
INPU
T
 
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
A2
Ambient Temperature
A1
 
 
 
 
Fig. 24-10 
Mounting 
Orientation  C  
(Table-top 
mounting) 
 
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1
A2
 
 
 
 
Fig. 24-11 
Mounting 
Orientation  D  
(Horizontal cw) 
Power
Supply
OUTPUT
IN
PU
T
 
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1
A2
 
 
 
 
Fig. 24-12 
Mounting 
Orientation  E  
(Horizontal ccw) 
Power Supply
OUTPUT
IN
PU
T
 
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1