Puls ML15.121 Power Supply Guia De Especificação

Página de 23
 
 
ML15.121
 
 
MiniLine-2 
 
12V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
 
 
P
OWER 
S
UPPLY
 
ƒ  100-240V Wide Range Input 
ƒ  NEC Class 2 Compliant 
ƒ  Adjustable Output Voltage 
ƒ  Efficiency up to 83% 
ƒ  Compact Design, Width only 22.5mm 
ƒ  Full Output Power Between -10°C and +60°C 
ƒ  Large International Approval Package 
ƒ  3 Year Warranty 
 
 
 
1/23
G
ENERAL 
D
ESCRIPTION
 
A compact size, light weight, simple mounting onto the 
DIN-rail and the utilization of only quality components 
are what makes the MiniLine power supplies so easy to 
use and install within seconds. 
A rugged electrical and mechanical design as well as a 
high immunity against electrical disturbances on the 
mains provides reliable output power. This offers 
superior protection for equipment which is connected 
to the public mains network or is exposed to a critical 
industrial environment. 
The MiniLine series offers output voltages from 5 to 
56Vdc and a power rating from 15W to 120W. 
The supplementary MiniLine decoupling diode module 
MLY10.241 allows building of redundant systems or to 
protect against back-feed voltages. 
 
 
S
HORT
-
FORM 
D
ATA
 
 
Output voltage 
DC 12V 
 
Adjustment range 
12 - 15V 
 
Output current 
1.3A at 12V 
1.0A at 15V 
 
Output power 
15W 
 
Output ripple 
< 75mVpp 
20Hz to 20MHz 
Input voltage 
AC 100-240V  
-15% / +10% 
Mains frequency 
50-60Hz  
±6% 
AC Input current 
0.28 / 0.17A 
at 120 / 230Vac 
Power factor 
0.51 / 0.44 
at 120 / 230Vac 
AC Inrush current 
typ. 16 /31A 
peak value at 
120/230Vac, 40°C 
and cold start 
DC Input 
88-375Vdc 
 
Efficiency 
83.0 / 82.5% 
at 120 / 230Vac 
Losses 
3.2 / 3.1W 
at 120 / 230Vac 
Temperature range -10°C to +70°C 
operational 
Derating 
0.4W/°C 
+60 to +70°C 
Hold-up time 
typ. 46 / 191ms 
at 120 / 230Vac 
Dimensions 22.5x75x91mm 
WxHxD 
Weight 
130g / 0.29lb 
 
 
 
O
RDER 
N
UMBERS
 
Power Supply  ML15.121 
12-15V Standard nit 
Accessory MLY10.241 
Redundancy 
module 
 
M
ARKINGS
 
 
 
UL 508 
 
UL 60950-1 
NEC Class 2
 
 
Class I Div 2
 
 
CSA 22.2 No107.1
 
 
Marine
 
 
EMC, LVD, RoHS
 
Mar. 2013 / Rev. 2.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany