Puls ML30.102 Power Supply Guia De Especificação
X Input
Input voltage
AC 100-240V (Wide Range), 47...63 Hz
Admiss. limits: AC 85...264V (DC 85...375V)
Admiss. limits: AC 85...264V (DC 85...375V)
Input current
<0.6A (@ AC 100V, 30W P
out
)
<0.25A (@ AC 240V, 30W P
out
)
External fusing
not required, unit provides internal fuse
(T3A15H, not accessible)
(T3A15H, not accessible)
Transient immunity
Transient resistance acc. to VDE 0160 / W2
(750V / 1.3ms), over entire load range
(750V / 1.3ms), over entire load range
Hold-up time
(see diagram below)
(see diagram below)
>170ms @ AC 230V, 10V / 3A
>100ms @ AC 196V, 10V / 3A
>18ms @ AC 100V, 10V / 3A
>100ms @ AC 196V, 10V / 3A
>18ms @ AC 100V, 10V / 3A
X Efficiency, Reliability
Efficiency
Losses
typ. 84%
(AC 230V, 10V / 3A)
(see also diagram below)
typ. 5.8W
typ. 5.8W
(AC 230V, 10V / 3A)
MTBF (Reliability)
appr. 650.000h acc. to Siemensnorm SN 29500
(10V / 3A, AC 230V, T
(10V / 3A, AC 230V, T
amb
= +40°C)
Prior to shipment, every unit undergoes the following tests in order to
isolate any defective units which might suffer an early failure:
• Run-in / burn-in (Full load, T
isolate any defective units which might suffer an early failure:
• Run-in / burn-in (Full load, T
amb
= +60°C, on/off cycle)
• Functional test (100%)
X Construction, Mechanics, Installation
Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid
on three housing sides to keep out small parts (e.g. screws), IP20
on three housing sides to keep out small parts (e.g. screws), IP20
Dimensions and weight
• W x H x D
• Weight
• W x H x D
• Weight
45mm x 75mm x 91mm (+ DIN Rail))
250g
250g
Mounting orientation
,
or
(cf. ’Output’)
Ventilation/Cooling
• Free space f. cooling
• Free space f. cooling
Normal convection, no fan required
recom’d.: 25mm on sides with ventilation grid
recom’d.: 25mm on sides with ventilation grid
Easy snap-on mounting onto the DIN Rail (TS35/7,5 or TS35/15).
Unit sits safely and firmly on the rail; no tools required even to remove
Unit sits safely and firmly on the rail; no tools required even to remove
Connection
by Spring Clamp terminals; uniformly firm hold,
vibration-resistant and maintenance-free.
vibration-resistant and maintenance-free.
Connector size range
• flexible cable
• solid cable
• flexible cable
• solid cable
• Wire strip length
0.3-2.5mm
2
(28-12 AWG)
0.3-4mm
2
(28-12 AWG)
Ferrules admissible
6mm (0.24in) recommended
6mm (0.24in) recommended
Design details – for your advantage:
• All terminals are easy to reach as mounted on the front panel.
• Input and output are strictly apart from each other (input below, out-
• All terminals are easy to reach as mounted on the front panel.
• Input and output are strictly apart from each other (input below, out-
put above) and so cannot be mixed up.
• Mounting and connection do not require any screwdriver
→ Easy, quick, durable and reliable installation.
• A jumper (output terminal) serves to adjust the output voltage
→ Easy, quick, durable and reliable installation.
• A jumper (output terminal) serves to adjust the output voltage
(10V resp. 12V).
X Diagrams
0
20
40
60
80
100
120
90
125
160
195
230
Input voltage V ACin [V]
Hol
d-up ti
me [ms]
Pout=30W, typ.
Pout=30W, min.
Pout=15W, typ.
Pout=15W, min.
Pout=30W, min.
Pout=15W, typ.
Pout=15W, min.
0
5
10
15
20
25
30
35
-10
0
10
20
30
40
50
60
70
Ambient temperature [°C]
Output power
[W
]
Output characteristic V
out
/I
out
(min.)
Efficiency
Hold-up time with ACin
(@ V
out
= 10V, typ.)
(at V
out
= 10V, typ. + min.)
0
2
4
6
8
10
12
14
0
1
2
3
4
5
6
Output current Iout [A]
O
u
tput
v
o
ltage Vout
[V
]
230VAC
100-120VAC
Vout range
Mounting
85-150 V ACin A-a A-b A-c
150-264 V ACin A-a A-a A-b
100-375 V DCin A-a A-a A-b
100-375 V DCin A-a A-a A-b
85-100 V DCin B-b B-b B-c
a
b
B
A
c
50
55
60
65
70
75
80
85
90
0,3 0,6 0,9 1,2 1,5 1,8 2,1 2,4 2,7 3 3,3
Output current Iout [A]
Ef
ficie
ncy [
%
]
120 V ACin
230 V ACin
230 V ACin
X Output
Output voltage
• preset
without jumper: DC 10-12V (adj. by front panel
potentiometer, adj. range guaranteed);
with jumper: 12V ±0.5%,
without jumper: 10V ±0.5%
potentiometer, adj. range guaranteed);
with jumper: 12V ±0.5%,
without jumper: 10V ±0.5%
Voltage regulation
stat. <1% @ V
out
= 10V
stat. <1.2% @ V
out
= 12V,
dyn. ±2.5% V
out
over all
Ripple
Noise (Spikes)
Noise (Spikes)
<2mV
PP
(200kHz bandw., 50
Ω measurem.)
<10mV
PP
(20MHz bandw., 50
Ω measurem.)
Overvoltage prot. (OVP) <18V
Rated continuous
loading
loading
at convection cooling:
max. I
max. I
out
= 3A @ V
out
= 10V,
max. I
out
= 2.5A @ V
out
= 12V,
details see derating diagram below
• power reserve
25%–40% (depending on V
in
);
details see diagr. 'output characteristic' below
Overload behaviour
Straight V/I characteristic (depending on V
in
);
details see diagr. 'output characteristic' below
Protection
Unit is protected against (also permanent)
short-circuit, overload and open-circuit.
short-circuit, overload and open-circuit.
Derating
depending on built-in orientation;
see diagram below
see diagram below
Power back immunity
30V
Operating indicator
Green LED (DC ON)
X Environmental Data, EMC, Safety
Ambient temperature range (measured 25mm below unit)
• storage/transport
• operation
• storage/transport
• operation
-25°C ... +85°C
-10°C ... +70°C (for derating see diagram below)
-10°C ... +70°C (for derating see diagram below)
Humidity
max. 95% (without condensation)
Electromagnetic
emissions (EME)
emissions (EME)
EN 61000-6-3 (includes EN 61000-6-4)
Class B (EN 55011, EN 55022)
Class B (EN 55011, EN 55022)
Electromagnetic
immunity (EMI)
immunity (EMI)
EN 61000-6-2 (includes EN 61000-6-1)
Safe low voltage:
Prot. class/degree:
Prot. class/degree:
SELV (EN60950, VDE0100/T.410), PELV (EN50178)
Class I (EN60950) / IP20 (EN60529)
Class I (EN60950) / IP20 (EN60529)
The PSU complies with all major safety approvals for EU (EN 60950,
EN 60204-1, EN 50178), USA (UL 60950, E137006, UL508 LISTED, E198865),
Canada (CAN/CSA-C22.2 No 60950 [CUR],CAN/CSA-C22.2 No. 14 [CUL]),
CB Scheme (IEC 60950). NEC Class 2 Power Supply and Hazardous Locati-
on Class I Div. 2 (UL 1604)
EN 60204-1, EN 50178), USA (UL 60950, E137006, UL508 LISTED, E198865),
Canada (CAN/CSA-C22.2 No 60950 [CUR],CAN/CSA-C22.2 No. 14 [CUL]),
CB Scheme (IEC 60950). NEC Class 2 Power Supply and Hazardous Locati-
on Class I Div. 2 (UL 1604)
Technical Data ML30.102
Product information (ML30e102), Rev.: 29. June 2004. Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They
are subject to change without prior notice.
PULS GmbH, Arabellastraße 15, D-81925 München X Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-299, E-Mail: sales@puls-power.com X www.puls-power.com
are subject to change without prior notice.
PULS GmbH, Arabellastraße 15, D-81925 München X Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-299, E-Mail: sales@puls-power.com X www.puls-power.com
Spri
ng C
lam
ps
Derating
of output power
of output power