Input
Input voltage
AC 100-240V (Wide Range), 47...63 Hz
Admiss. limits: AC 85...264V (DC 85...375V)
Input current
<0.6A (@ AC 100V, 30W P
out
)
<0.25A (@ AC 240V, 30W P
out
)
External fusing
not required, unit provides internal fuse 
(T3A15H, not accessible)
Transient immunity
Transient resistance acc. to VDE 0160 / W2 
(750V / 1.3ms), over entire load range
Hold-up time
(see diagram below)
>170ms @ AC 230V, 10V / 3A 
>100ms @ AC 196V, 10V / 3A 
>18ms @ AC 100V, 10V / 3A 
Efficiency, Reliability
Efficiency 
Losses
typ. 84%
(AC 230V, 10V / 3A)
(see also diagram below)
typ. 5.8W
(AC 230V, 10V / 3A)
MTBF (Reliability)
appr. 650.000h acc. to Siemensnorm SN 29500
(10V / 3A, AC 230V, T
amb
 = +40°C)
Prior to shipment, every unit undergoes the following tests in order to 
isolate any defective units which might suffer an early failure:
• Run-in / burn-in (Full load, T
amb 
= +60°C, on/off cycle)
• Functional test (100%)
Construction, Mechanics, Installation
Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid 
on three housing sides to keep out small parts (e.g. screws), IP20
Dimensions and weight
• W x H x D
• Weight
45mm  x  75mm  x  91mm (+ DIN Rail))
250g
Mounting orientation
 
or
 
 
(cf. ’Output’)
Ventilation/Cooling
• Free space f. cooling
Normal convection, no fan required
recom’d.: 25mm on sides with ventilation grid
Easy snap-on mounting onto the DIN Rail (TS35/7,5 or TS35/15).
Unit sits safely and firmly on the rail; no tools required even to remove
Connection
by Spring Clamp terminals; uniformly firm hold, 
vibration-resistant and maintenance-free.
Connector size range
• flexible cable
• solid cable
• Wire strip length
0.3-2.5mm
2
 (28-12 AWG)
0.3-4mm
(28-12 AWG)
Ferrules admissible
6mm (0.24in) recommended
Design details – for your advantage:
• All terminals are easy to reach as mounted on the front panel.
• Input and output are strictly apart from each other (input below, out-
put above) and so cannot be mixed up.
• Mounting and connection do not require any screwdriver
→ Easy, quick, durable and reliable installation.
• A jumper (output terminal) serves to adjust the output voltage 
(10V resp. 12V).
Diagrams
0
20
40
60
80
100
120
90
125
160
195
230
Input voltage V ACin [V]
Hol
d-up ti
me [ms]
Pout=30W, typ.
Pout=30W, min.
Pout=15W, typ.
Pout=15W, min.
0
5
10
15
20
25
30
35
-10
0
10
20
30
40
50
60
70
Ambient temperature [°C]
Output power
 [W
]
Output characteristic V
out
/I
out
(min.)
Efficiency 
Hold-up time with ACin 
(@ V
out
 = 10V, typ.)
(at V
out
 = 10V, typ. + min.)
0
2
4
6
8
10
12
14
0
1
2
3
4
5
6
Output current Iout [A]
O
u
tput
 v
o
ltage Vout
 [V
]
230VAC
100-120VAC
Vout range
Mounting
85-150 V ACin A-a A-b A-c
150-264 V ACin A-a A-a A-b
100-375 V DCin A-a A-a A-b
85-100 V DCin B-b B-b B-c
a
b
B
A
c
50
55
60
65
70
75
80
85
90
0,3 0,6 0,9 1,2 1,5 1,8 2,1 2,4 2,7 3 3,3
Output current Iout [A]
Ef
ficie
ncy [
%
]
120 V ACin
230 V ACin
Output
Output voltage
• preset
without jumper: DC 10-12V (adj. by front panel 
potentiometer, adj. range guaranteed);
with jumper: 12V ±0.5%,
without jumper: 10V ±0.5%
Voltage regulation
stat. <1% @ V
out
 = 10V
stat. <1.2% @ V
out 
= 12V,
dyn. ±2.5% V
out
 over all
Ripple
Noise (Spikes)
<2mV
PP
  (200kHz bandw., 50 
Ω measurem.)
<10mV
PP
(20MHz bandw., 50 
Ω measurem.)
Overvoltage prot. (OVP) <18V
Rated continuous 
loading
at convection cooling:
max. I
out
 = 3A @ V
out
 = 10V,
max. I
out
 = 2.5A @ V
out
 = 12V, 
details see derating diagram below
• power reserve
25%–40% (depending on V
in
);
details see diagr. 'output characteristic' below
Overload behaviour
Straight V/I characteristic (depending on V
in
);
details see diagr. 'output characteristic' below
Protection
Unit is protected against (also permanent) 
short-circuit, overload and open-circuit. 
Derating
depending on built-in orientation;
see diagram below
Power back immunity
30V
Operating indicator
Green LED (DC ON)
Environmental Data, EMC, Safety
Ambient temperature range (measured 25mm below unit)
• storage/transport
• operation 
-25°C ... +85°C
-10°C ... +70°C (for derating see diagram below)
Humidity
max. 95% (without condensation)
Electromagnetic 
emissions (EME)
EN 61000-6-3 (includes EN 61000-6-4) 
Class B (EN 55011, EN 55022)
Electromagnetic 
immunity (EMI)
EN 61000-6-2 (includes EN 61000-6-1)
Safe low voltage: 
Prot. class/degree: 
SELV (EN60950, VDE0100/T.410), PELV (EN50178)
Class I (EN60950) / IP20 (EN60529) 
The PSU complies with all major safety approvals for EU (EN 60950, 
EN 60204-1, EN 50178), USA (UL 60950, E137006, UL508 LISTED, E198865), 
Canada (CAN/CSA-C22.2 No 60950 [CUR],CAN/CSA-C22.2 No. 14 [CUL]), 
CB Scheme (IEC 60950). NEC Class 2 Power Supply and Hazardous Locati-
on Class I Div. 2 (UL 1604)
Technical Data ML30.102
Product information (ML30e102), Rev.: 29. June 2004. Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They 
are subject to change without prior notice.
PULS GmbH, Arabellastraße 15, D-81925 München X  Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-299, E-Mail: sales@puls-power.com X  www.puls-power.com