Puls ML60.121 Power Supply Guia De Especificação

Página de 23
 
 
ML60.121
 
 
MiniLine-2 
 
12V,
 
4.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
15.  P
ROTECTION 
F
EATURES
 
 
Output protection 
Electronically protected against overload, no-load and short-circuits 
*)
 
Output over-voltage protection typ. 
18Vdc 
max. 19Vdc 
In case of an internal power supply fault, a redundant 
circuit limits the maximum output voltage. In such a 
case, the output shuts down and stays down until the 
input voltage is turned off and on again. 
Output over-current protection electronically 
limited 
 
Degree of protection 
IP 20 
EN/IEC 60529 
Penetration protection 
> 2.5mm in diameter 
e.g. screws, small parts 
Over-temperature protection 
not included 
 
Input transient protection 
MOV 
Metal Oxide Varistor 
Internal input fuse 
T3.15A H.B.C. 
not user replaceable 
*)   In case of a protection event, audible noise may occur. 
 
 
16.  S
AFETY 
F
EATURES
 
 
Input / output separation 
*)
 SELV 
IEC/EN 
60950-1 
 
PELV 
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 
Class of protection 
PE (Protective Earth) connection required 
 
II (with restrictions) 
for use without PE connection contact PULS 
Isolation resistance 
> 5MOhm 
Input to output, 500Vdc  
Touch current (leakage current) 
typ. 0.13mA / 0.29mA 
100Vac, 50Hz, TN-,TT-mains / IT-mains 
 
typ. 0.19mA / 0.40mA 
120Vac, 60Hz, TN-,TT-mains / IT-mains 
 
typ. 0.30mA / 0.63mA 
230Vac, 50Hz, TN-,TT-mains / IT-mains 
 
< 0.17mA / 0.38mA 
110Vac, 50Hz, TN-,TT-mains / IT-mains 
 
< 0.25mA / 0.53mA 
132Vac, 60Hz, TN-,TT-mains / IT-mains 
 
< 0.41mA / 0.85mA 
264Vac, 50Hz, TN-,TT-mains / IT-mains 
*)   Double or reinforced insulation 
 
Mar. 2013 / Rev. 1.2  DS--ML60.121-EN 
All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
13/23