E.J. Ward Inc. HM-900M Manual Do Utilizador

Página de 5
Page 3 of 5 
Revision 2.11 Revised: 
1/27/2011 
 
PROGRAMMING   
   
1. The installer must obtain unique identification numbers for the hose modules so its FCT will know 
which hose the VIT/Canceiver data came from.  Hose module identification consists of three 
numbers: System NumberTerminal Number, and Hose Number.    
2. Hose modules are programmed with the same Palmtop Programmer used to program VIT/Canceiver 
units. On the palmtop, exit the VIT/Canceiver Setup program using Menu 8.   
3. At the DOS prompt, type HOSE and press <Enter>.     
4. The Hose Module Setup Main Menu should appear (Figure 5.)   
5. Press the <Space> bar and point the front edge (edge closest to the logo) of the hose module at the 
palmtop’s interface card (Figure 6.)    After a short delay, the palmtop should beep and display the 
module’s current configuration.   
6. If the module seems to not respond in Step 5, gently shake the module and retry Step 5.   
7.  Enter the correct System Number, Terminal Number, and Hose Number for the hose module. The 
‘Prompt Type’ setting determines what type of data is requested from the VIT/Canceiver.    If unsure 
of the correct setting, set ‘Prompt Type’ to ‘EEPROM’.   
8. After entering all data, the bottom line of the screen should display ‘Update Hose Module or Exit’.    If 
this line is not present, press <Enter> repeatedly until it is displayed. The left and right arrow keys 
will highlight the two different options. With ‘Update Hose Module’ highlighted, press <Enter> to 
send the new configuration data to the hose module. Again, point the front edge of the module at the 
palmtop’s interface card.  After a short delay, the palmtop should beep, indicating a new 
configuration has been accepted.       
9.  Test the hose module with a good VIT/Canceiver or the VIT/Canceiver simulator function of the 
VIT/Canceiver palmtop program.     
10. Exit the hose module program by pressing the escape key repeatedly. The hose module program will 
respond with “bye!” when it exits to DOS.  Type VIT and press <Enter> to get back into the 
VIT/Canceiver program.   
11. If problems are still experienced, review the back of the VIT Installation Guide V2.11 – Section   
5.3 - Troubleshooting Hose Module Equipped Fuel Island, or call Ward Inc. at 210-824-7383