PTM 33X / PTM 33XC / PTM 330U 
3.7  Radio telegram 
3.7.1  Normal operation 
In default configuration PTM 33x transmits the same telegrams as a PTM 200 radio switch: 
 
  Telegram type RPS: There are two message types depending on how many buttons 
(A0, A1, B0, B1) have been pressed (connected to GND) 
o  N-message: Only one or two buttons have been pressed. 
o  U-message: No pushbutton was pressed when activating the energy genera-
tor, or more than two pushbuttons have been pressed. 
  Unique factory programmed 32 bit ID 
  DATA_BYTE2, DATA_BYTE1, DATA_BYTE0=0 
  DATA_BYTE3 and STATUS as follows: 
 
 
 
N-message: 
 
DATA_BYTE3: 
 
7                                                                0 
RID 
UD 
PR 
SRID 
SUD  SA 
 
RID 
(2 bit) 
Rocker ID, A=0, B=1  
UD 
(1 bit) 
UD=1  O-button, UD=0  I-button 
PO 
(1 bit) 
Polarity, see table below 
SRID 
(2 bit) 
Second Rocker ID 
SUD 
(1 bit) 
(Second) SUD=1  O-button, SUD=0  I-button 
SA 
(1 bit) 
SA=1  Second action (2 buttons pressed  
                                                simultaneously), SA=0  No second action 
 
STATUS: 
 
7                                                                0 
Reserved  T21  NU 
RP_COUNTER 
 
Reserved 
(2 bit)  
For future use 
T21 
(1 bit) 
NU 
(1 bit) 
NU=1  N-message. 
RP_COUNTER 
(4 bit) 
Repeater level: 0 is original message (not repeated)