EnOcean GmbH STM310C Manual Do Utilizador

Página de 55
USER MANUAL V0.60 
© 2010 EnOcean  |  www.enocean.com
STM 330 / STM 330C User Manual V0.60  |  Page 19/27
 
 
STM 330 / STM 330C
Calculations are performed on the basis of electric charges because of the internal linear 
voltage regulator of the module. Energy consumption varies with voltage of the energy 
storage while consumption of electric charge is constant. 
 
 
From these values the following performance parameters have been calculated: 
 
Wake 
cycle 
[s] 
Transmit 
interval 
Operation Time  
in darkness [h] 
when storage 
fully charged  
Required reload 
time [h] at 200 
lux within 24 h 
for continuous 
operation 
24 h operation 
after 6 h  
illumination  
at x lux 
Illumina-
tion level 
in lux for 
continuous 
operation 
Current 
in µA 
required 
for con-
tinuous 
operation
0.5 
storage too sm all  storage too sm all 
5220 
130.5
10 
1.7 
storage too sm all  storage too sm all 
1620 
40.5
100 
2.1 
storage too sm all  storage too sm all 
1250 
31.3
10 
5.1 
storage too sm all  storage too sm all 
540 
13.5
10 
10 
16 
21 
700 
175 
4.4
10 
100 
20 
16.8 
560 
140 
3.5
100 
43 
7.8 
260 
65 
1.6
100 
10 
98 
3.6 
120 
30 
0.8
100 
100 
112 
100 
25 
0.6
 
Assumptions:   
„ 
Internal storage PAS614L-VL3 with 0.25 F, Umax=3.2 V, Umin=2.2 V, T=25 °C  
„ 
Consumption: Transmit cycle 100 µC, measurement cycle 30 µC 
„ 
Pre-installed solar cell ECS 300, operating values 3 V and 5 µA @ 200 lux fluorescent 
light  
„ 
Current proportional to illumination level (not true at very low levels!) 
 