Performing Remote Analysis (TNS)
The CCE has the capability to decide the quality of a TC reading based on the 
Hour of Reading and Configuration field in the status byte of the Total 
Consumption registers.
If the Hour of Reading and Configuration field is equal to zero, the CCE marks the 
TC data as suspect. If this is the case, there is no EMTR-3 present.
If the Hour of Reading and Configuration field is equal to twenty five, the CCE 
marks the quality of TC data appropriately.
If this is the case, the time and date stamp for the data is more than twenty four 
hours old.
When the Hour of Reading and Configuration is equal to twenty five or twenty 
six, the CCE uses the current date and time to mark when the TC data was received 
at the master station.
If the Hour of Reading and Configuration field is equal to twenty six, the CCE 
marks the quality of TC data appropriately based on the utility configured quality 
rules. If this is the case, the time and date stamp for the data is invalid.
If the Hour of Reading and Configuration field is equal to thirty, the CCE marks 
the TC data as suspect. If this is the case, an IED is installed but no data has been 
received yet.
If the Hour of Reading and Configuration field is equal to thirty one, the CCE 
marks the TC data as suspect. If this is the case, there is no IED installed on this 
port.
IED Configuration Data Files
TNS has the capability to produce IED Configuration Data files, as defined in this 
section, for export to other applications. The IED Configuration Data export file is 
composed of a number of records.
Each data record in the IED Configuration Data export file contains the data fields 
listed in Table 2.
Each data record in the IED Configuration Data export file always populates the 
following fields: Meter Number, Serial Number, Serial Port and Device Type.
Any field in an IED Configuration Data record that is not populated is left blank. 
The IED Configuration Data export file is a delimited file constructed by 
sequentially delimited data records. The comma and vertical pipe characters are 
valid delimiters for an IED Configuration Data export file.
Each data record in the IED Configuration Data export file is separated by a 
line-feed and carriage return character (in that order).
DRAFT