PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013  
35
Operations
FWSG
ADDRESS
FAULT
AD FLT
Non-
latching
There is either a device in 
the mesh set to address 
0, or there is a duplicate 
address used for another 
wireless module at the 
address of the FWSG.
The offending device (detector 
or module set at address 0 or 
module at the same address 
as the FWSG) will be indicating 
the LED pattern for address 
fault.  Find and resolve that 
device.
MAX 
GATEWAYS
MAX GW
Non-
latching
Wireless communication 
reliability is compromised 
due to the installation 
limits of Honeywell 
wireless systems being 
exceeded.
Investigate for overlapping or 
adjacent wireless systems 
produced by Honeywell.  
Reduce the instances of 
overlap by removing systems, 
or devices in the overlapping 
region.  Refer to 2.7.8 "Multiple 
Wireless Sensor Network 
Installation Restrictions" on t
he 
installation limits for the 
Honeywell wireless system. 
RF DEV NO 
ANSWER
RF DEV
Latching 
trouble; 
remains 
active for 
the first 180 
seconds 
before it 
can be 
cleared with 
a system 
reset.
A wireless device that 
was part of the mesh has 
dropped from the mesh.
Initiate a system reset at the 
FACP at least 3 minutes after 
the trouble was initiated to 
clear.
If the device was intentionally 
removed, no further action is 
needed.
If the device was not 
intentionally removed; refer to 
panel history or active panel 
troubles to investigate the 
cause of the disturbance.
NFS2-3030
NCA-2
Onyxworks
NFS2-640
NFS-320
Description
Course of Action