Install Hardware
Figure 4-9 4G V-Flex Lite and 4G CR-Pass - Pin-out Diagram
When connecting the device to the network, the following procedures must be followed:
 Use Category 5 cabling with a characteristic impedance of 120 ohms for RS-
485 networks. Category 5 cables with a characteristic impedance of 100
ohms can also be used, but with lower performance.
 Cable manufacturers provide cables with multiple twisted pairs designed for
this type of communication (characteristic impedance is 120 ohm).
 Unused pairs within the cable must be terminated with characteristic
impedance (100 or 120 ohm) on both ends.
 AWG 24 should be considered as the minimum gauge.
 Choose one twisted pair of conductors to use for RS-485 differential
connections, other conductors should be used for Signal Ground (RS-485
GND on Weidmuller connection).
 The RS-232 to RS-485 converter must support Sense Data to be able to
switch from Send to Receive mode.
 Check each device's cabling for ground faults before connecting to an RS-
485 network.
 Each device should have pin 3 of the mini-connector connected to earth
ground.