Planning the Installation
Installation of locks and access controllers should be completed according to their respective
manufacturers' specifications and in accordance with all local codes. Final connections to the
device are explained in more detail in Chapter 4.
To avoid externally generated transients, do not run any wires near utility AC power wiring,
lightning rod grounding wire, etc. Grounding equipment is required for ESD protection and
safety.
2.1.6 CHOOSE NETWORK TYPE
If your installation requires the use of network communications, then the choice of cable, the
cable run length, the network topology, and the termination of the network are important
aspects that must be considered. The 4G V-Flex Lite and CR-Pass devices can be
networked using RS-232, RS-485, or Ethernet protocols.
The table below outlines relevant parameters of the RS-485, RS-232, and 100 baseT
Ethernet communication protocols.
Table 2-1 Communications Network Comparison
Spec
RS-485
100BaseT
Mode of Operation
Differential DC
Coupled
Multi
DC Isolation
No
No
Maximum Distance
4000 feet
330 feet
Number of Devices
on one line
31
Unlimited
Maximum Data
Rate
57600 bps
(recommended)
Auto-
negotiated
2.1.6.1 RS-485
RS-485 has two distinct advantages over the more common RS-232. First, it allows you to
connect up to 31 4G V-Series devices to a PC with an external RS-232 to RS-485 converter
(available from L-1 Identity Solutions). Second, the RS-485 specification allows for cable run
lengths up to 4000 feet (1200 meters) at modest baud rates.
An RS-485 network is required instead of RS-232 if:
 Multiple devices must be connected together so that templates can be
distributed among the devices
 The installation has only a single device, but it is over 150 feet (45 meters)
from the host PC.