Planning the Installation
2.1.7 CHOOSE POWER SOURCE
4G V-Flex Lite, CR-Pass and SecureControl devices can be powered by several methods:
 12V DC regulated (4G V-Flex Lite, CR-Pass and SecureControl)
 Power Over Internet (PoE) through an inline PoE 802.3af power injector (4G
CR-Pass only)
Power sources should be:
 Isolated from other equipment
 Filtered
 Protected by an Uninterruptible Power Supply (UPS) or battery backup
 Protected by a voltage suppression device if transient electrical surges are
an issue in the location.
When planning a system, know the power requirement of each device. If multiple devices are
to share a common power supply, exercise care to avoid excessive voltage loss on the wires.
Voltage loss can lead to communication problems when devices are talking and/or listening
on different ground references.
Voltage loss is directly proportional to wire resistance and the current the wire carries. Always
place the device as close as possible to the power supply and always select a wire size
appropriate for the load. 4G Lite devices run on DC power between 12 V and 24 VDC.
Power requirements for all 4G V-Flex Lite, CR-Pass and SecureControl models are listed
below: