 Unit Installation
NetVanta 1000/1000R Series Hardware Installation Guide
 54
Copyright © 2007 ADTRAN, Inc.
61200500L1-34L
Figure 34.  Grounding the NetVanta 1224STR (DC)
Installing Dial Backup and Network Interface Modules
The DIM plugs on to the NIM. The NIM is then installed into the rear panel option module slot. The following 
tables list the installation steps. Also see Figure 35 on page 55 and Figure 36 on page 56.
To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a 
DC-C (common) bonding and grounding environment. It may not be utilized in a DC-I 
(isolated) bonding and grounding environment.
For NetVanta modules with outside plant connections, ensure that all cables are 
removed from the module before installing or removing it from the NetVanta chassis.
Always remove power from the unit prior to removing or installing a module.
Improper installation may result in damage to the modules.