Itron Inc. CCU100A Manual Do Utilizador

Página de 132
 
Sample Sweeps Output 
 
TDC-0971-011 CCU 100 and Repeater 100 Installation Guide 
111 
 
Proprietary and Confidential 
 
Down Conductor Installation 
Each down conductor must consist of 4/0 AWG stranded copper with green insulation. 
Preferably, install the down conductor without conduit. If a conduit is required by local 
standards or by the landlord, then a non-metallic PVC conduit is preferred. If a metallic 
conduit is required, use the threaded type and install grounding bushings on both ends to 
bond the conduit with a minimum of No. 2 AWG stranded copper conductor to the 
ground bar at each end. The metallic conduit must be bonded at both ends to a ground bar 
to prevent a choke effect in the event of a surge. 
A low halogen cable that meets the ratings of Telcordia GR-347 is acceptable. Place the 
MGB bar as close as possible to the equipment cabinets and the path to ground options 
(for example, ground rod, cold water pipe, or building steel). Install the ground bar to 
ensure that the wire bending radii for the 4/0 AWG and No. 2 AWG are a minimum of 12 
inches and that all paths to ground travel flat or down. 
 
Warning  Never allow a path to ground to travel upward. 
 
 
Cold Water Pipe Option 
The location of the cold water main is usually in the basement or in the mechanical room 
of the building. When attaching to the pipe, the clamp must come into contact with a 
minimum of 4 linear inches of pipe or utilize a Burndy GAR clamp. 
 
To ground a cold water pipe 
1.  Drill the clamp to accept a two-hole ½ inch hardware lug. You can also connect the 
water pipe by attaching the ground conductor using an approved water pipe clamp. 
2.  Scrape clean the area of contact to the cold water pipe with the clamp. The area  must 
be free of paint, rust and/or corrosion and coated with an approved anti-oxidation 
compound before the clamp is attached to the pipe. 
3.  Locate the clamp on the interior of the building, within five feet of the cold water pipe 
entry point into the building, without any flanges, or pipe connections between the 
ground clamp and the pipe building entry point. 
Note  This is required to ensure good continuity to ground at the point of pipe contact 
and building entry. 
4.  If the connection is made on the output side of the water meter, you can install an 
electrical jumper (minimum 4/0 AWG) around the meter to another clamp to provide 
a continuous path to ground, in the event the water meter is removed for service. 
 
Building Steel Option 
When attaching to building steel for a grounding path, use exothermic weld connections 
installed per manufacturer’s recommendation.