Lightning Arrestor 
 
 CCU 100 and Repeater 100 Installation Guide 
 
11 
 
Proprietary and Confidential 
 
The recommended procedure for grounding the antenna system is as follows:  
•  Mount a copper ground bar near the antenna. This is the top ground bar.  
•  Mount a second copper ground bar near the CCU/Repeater. This is the bottom ground 
bar.  
•  Connect the two ground bars with a #6 gauge green jacketed stranded wire or a #2 
solid copper wire.  
•  Ground the antenna mount and the top coaxial ground kit to the top ground bar.  
•  Ground the bottom coaxial ground kit and the lightning arrestor to the bottom ground 
bar.  
•  Connect the bottom ground bar to one or more earth ground rods.  
•  All ground wires should be connected straight to ground, with no right angle turns or 
sharp bends in the wires.  
•  Install ground leads on coaxial grounding kits without loops or bends and install 
grounding kits in the proper orientation per the manufacturer's specifications.  
 
Lightning Arrestor 
A lightning arrestor (or surge protector) capable of withstanding multiple lightning strikes 
should be installed when using a remote mount antenna. This helps protect the 
CCU/Repeater in the event of a lightning strike.  
The lightning arrestor is fitted to the coaxial antenna cable at the SURGE end and the RF 
jumper cable that connects to the CCU/Repeater module at the PROTECTED end. It 
includes a bulkhead connector interface that mounts to a ground plate with a washer and 
nut. The arrestor is also furnished with a ground lug, if your installation does not have 
provisions for a ground plate. The ground lug on the arrestor is designed for #2AWG solid 
or stranded wire. The ground wire must be crimped to this lug, never soldered. 
 
Caution  The lightning arrestor must be connected to an earth-ground.