Section 8: LE4000 Wiring Diagrams
Figure 8-2 Telephone Connection
R
E
D
 (R
)
G
R
E
E
N
 (T
)
G
R
A
 (R
)
B
R
O
W
N
 (T
)
RJ-31X
R
IN
G
T
IP
CONTROL PANEL
Incoming
Phone line
Handset
  R
I
T
I
T
I
R
I
T
IP
R
IN
G
LE4000
TIP
RING
T1
R1
Z2
PGM2
DC IN
+
-
1
2
3
4
7
9
8
10
Figure 8-3 Power Supply and Supervision Wiring Diagram
Control 
Panel 
EOL 
Resistor 
See Note 3 
CONTROL PANEL
DSC 
Supervision 
Relay 
See Note 2
DSC
RM-2 
RELA
Y
NC
C
NO
+12VDC
GND
Aux Power
+    -
LE4000
(BLK/WHT)  +13.8VDC
(BLK )  GND
DSC 
ADP
 1310W
-NA(U)
Power 
Adaptor
TIP
RING
T1
R1
Z1
PGM1
Z2
PGM2
DC IN
+
-
1
2
3
4
5
6
7
9
ZONE 
TERMINALS
(See Note 1)
-    +
   
8
10
NOTES
1. 
Program  the  Zone/Point  as  “Supervisory”  type
with  keypad  only  annunciation  when  in  Alarm.
Do NOT use a point that is normally used for
2-Wire Smoke detectors.
2. The power Supervision relay, RM-2 is only used
when the LE4000 is not powered by the control
panel. When the Radio is powered by the control
panel  the  relay  is  not  required  since  a  loss  of
input power will generate a signal to the CMC.
3. PGM2  on  the  LE4000  must  be  set  as  “Active 
High” (default).
4. When powering the LE4000 Radio by an Auxiliary
Power  supply  that  has  its  own  backup  battery,
remove the battery that came with the radio.