Digital Security Controls Ltd. 18LE2077 Manual Do Utilizador

Página de 51
25
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above)
for details on settings.
[028] Cellular 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above)
for details on settings.
[029] Cellular 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See System Test Options (above)
for details on settings.
NOTE: The time interval (in minutes) between periodic tests is programmed in Section [125]
(Ethernet) and Section [225] (Cellular).
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an
FTC Trouble on the system restores.
[031] Priority Tamper Alarm
Program 00 to disable this event or FF to enable. This event will occur when panel tampered 
during the entry delay.
[032] Priority Tamper Restore
Program 00 to disable this event or FF to enable.This event will occur when panel tamper 
restored.
[033] Communicator Firmware Update Begin
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when the 
communicator firmware update begins.
[034] Communicator Firmware Update Successful
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when the 
communicator firmware update successfully completed.
[035] Panel Firmware Update Begin
Default (FF);
Program 00 to disable this event transmission or FF to enable. This event will occur when the 
panel firmware update begins.
Table 11: Priority Tamper/Tamper Restore
Event
SIA 
Identifier
SIA 
Reporting 
Code
Contact ID 
Qualifier
Contact ID 
Event 
Code
Contact ID 
Reporting 
Code
Contact 
ID User/
Zone
Priority Tamper
BA
000
1
1
37
000
Priority Tamper 
Restore
BR
000
3
1
37
000