ADC Telecommunications Inc. FWURHSMR2 Manual Do Utilizador
Mailing Address: P.O. Box 1101, Minneapolis, Minnesota 55440-1101
World Headquarters: Minneapolis, Minnesota USA +1.952.938.8080 www.adc.com
AC Power Wiring Installation
A 15-foot connectorized 3-wire cable is provided for the AC power connections. The connectorized end
of the cable connects to the AC power port located on the bottom of the enclosure. The stub end of the
cable must be routed to an external junction box (not provided) for permanent connection to the AC
power system wiring. The socket outlet shall be installed near the equipment and shall be easily
accessible.
of the cable connects to the AC power port located on the bottom of the enclosure. The stub end of the
cable must be routed to an external junction box (not provided) for permanent connection to the AC
power system wiring. The socket outlet shall be installed near the equipment and shall be easily
accessible.
The AC power source must supply 120 or 240 VAC, 50 or 60 Hz, single-phase power through a
15 Amp circuit breaker. The AC power cable provides three wire leads for line, neutral, and
ground connections. The power cable is rated for indoor or outdoor use and must not be placed
within electrical conduit as this will impede the cooling of the cable during usage. The electrical
junction box and any conduit, wire, and fittings required must be provided by the installer.
Use the following procedure to install the AC power wiring:
1. Locate the AC power cable that is provided separately with the enclosure.
2. Route the power cable between the AC power port, located on the underside of the enclosure
and the nearest AC power junction box as shown in
2. Route the power cable between the AC power port, located on the underside of the enclosure
and the nearest AC power junction box as shown in
Figure 14
. It may be necessary to install a
new junction box if an existing junction box is not available.
Figure 14. Typical AC Power Cable Routing