WARNING: Disconnect primary power prior to servicing.
Section 1 Introduction
Maxiva ULX ATSC Series
User Manual
1.2.8.1
Cooling System Control Panel
The cooling system control panel controls the operation of the pump module/heat 
exchanger, and sends fault and status information to the TCU. The cooling system 
control connects to the RF Detector/Pump Control/Interlocks card in the TCU for 
monitoring and control. 
NOTE:
The  control panel and pump module is designed for indoor use only.
The pump control signals are described below:
 +12 Vdc  - Voltage supplied by Pump Control Unit.  
PUMP_INTLK - Output, active high. When high, the transmitter’s RF output is muted 
and the pumps are forced to OFF regardless of the LOCAL/
REMOTE setting in the pump cooling control panel. If this interlock 
is active, the pumps can’t be turned ON (even locally). This interlock 
is driven by the transmitter or PA cabinet leak detector. If a leak is 
detected, this interlock goes to high.
PUMP RUN - Output, active high to turn on selected pump.
SWITCH PUMP - Output, pulsed active high to switch between Pump A and Pump B.
PUMP A SELECTED - Input, connect to open drain or relay contacts. Active when 
input is LOW. 
PUMP B SELECTED - Input, connect to open drain or relay contacts. Active LOW. 
LOCAL STATUS - Input, connect to open drain or relay contacts.   Remote = HIGH, 
Local = LOW