DigiReader DR4208K Installation Notes
P/N 7600051 Rev. A 6/28/02 Page 1 of 2
DIGIREADER DR4208K INSTALLATION NOTES
DIP ADDRESS SWITCH
The DR4208K reader has a 10-position DIP-switch S1, (as shown
to the right, with S-NET address 1 selected for 9600 S-NET baud).
to the right, with S-NET address 1 selected for 9600 S-NET baud).
INTERNAL INTERFACE CABLE
An attached pigtail cable assembly provides the connection from the printed-circuit assembly
to the access control unit wiring on a DigiReader DR4208K. The cable is color-coded as follows:
to the access control unit wiring on a DigiReader DR4208K. The cable is color-coded as follows:
*
For tolerance reasons, the UL tested voltage range is 12.5 to 24VDC +/-15%.
Switch S1 Settings
S-NET Address/
Function
Switch S1 Settings
S-NET Address/Function
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
Off Off Off Off Off Off
X X EOL Off-line 0
Off Off Off On On Off
X X X 24
On Off Off Off Off Off
X X X 1
On Off Off On On Off
X X X 25
Off On Off Off Off Off
X X X 2
Off On Off On On Off
X X X 26
On On Off Off Off Off
X X X 3
On On Off On On Off
X X X 27
Off Off On Off Off Off
X X X 4
Off Off On On On Off
X X X 28
On Off On Off Off Off
X X X 5
On Off On On On Off
X X X 29
Off On On Off Off Off
X X X 6
Off On On On On Off
X X X 30
On On On Off Off Off
X X X 7
On On On On On Off
X X X 31
Off Off Off On Off Off
X X X 8
Off On Off On Off On
X X X Wiegand I/F (26-bit - 2A HEX) 2-LEDs
On Off Off On Off Off
X X X 9
On On Off On Off On
X X X Wiegand I/F (34-bit - 2B HEX) 2-LEDs
Off On Off On Off Off
X X X 10
Off Off On On Off On
X X X Wiegand I/F (26-bit - 2C HEX) 1-LED
On On Off On Off Off
X X X 11
On Off On On Off On
X X X Wiegand I/F (34-bit - 2D HEX) 1-LED
Off Off On On Off Off
X X X 12
Off On On On Off On
X X X TEST Mode - 2E HEX
On Off On On Off Off
X X X 13
On On On On Off On
X X X DEMO Mode - 2F HEX
Off On On On Off Off
X X X 14
Off Off Off Off On On
X X X Wiegand I/F (42-bit - 30 HEX) 1-LED
On On On On Off Off
X X X 15
Off Off
DKR ONLY
Off Off Off Off On Off
X X X 16
On Off
DKR + VIP
On Off Off Off On Off
X X X 17
Off On
MSR+VIP (MSRK)
Off On Off Off On Off
X X X 18
On On
Wiegand S-NET
On On Off Off On Off
X X X 19
Off X 9600 S-NET Baud
Off Off On Off On Off
X X X 20
On X 19200 S-NET Baud
On Off On Off On Off
X X X 21
Off No End of Line Terminator
Off On On Off On Off
X X X 22
On End of Line Terminator
On On On Off On Off
X X X 23
COLOR FUNCTION
(S-NET Use)
(Wiegand Use)
Red
+10.8 to +28VDC
*
(max. draw 130mA)
S-NET Nominal
Wiegand Nominal
Green S-NET A
For use with NexWatch
access control panels
NA
White S-NET B
Black GND
Black GND
S-NET DC Return
Wiegand DC Return
Shield Earth
S-NET Shield
Wiegand Shield: Tied to Wiegand DC Return
Blue
Data 0 (Out 0)
NA
For use with Wiegand access control panels
Orange Data 1 (Out 1)
Yellow LED 0
Yellow LED 0
(Green) Both LEDs are ACU-controlled
and are ON/low or OFF/high
Brown LED 1
(Red)